CU/MICA/GF/CCS
BS 6387, EN50200, IEC60332-1 & IEC60332-3, IEC60331, or other standards on request.
YTTW cables are specified for critical safety circuits where power continuity during a fire is non-negotiable:
High-rise buildings & commercial complexes,Transportation infrastructure,Data centers & IT facilities,Industrial & energy facilities,Healthcare facilities.
| ① Conductor | Stranded Copper wire |
| ② Insulation | Mica tape (MICA/MT) |
| ③ Filling | Glass fiber (GF) |
| ④ Sheath | Corrugated copper sheath (CCS) |
| Fire resistant power cable, 0.6/1kV, CU/MICA/GF/CCS |
|||
| Conductor | Insulation | ||
| Nominal area |
No./diam. of strand |
Diam. of conductor |
Thickness |
| (mm²) | (no./mm) | (mm) | (mm) |
| Single core | |||
| 1.5 | 7/0.53 | 1.6 | 0.7 |
| 2.5 | 7/0.67 | 2.0 | 0.7 |
| 4 | 7/0.85 | 2.6 | 0.7 |
| 6 | 7/1.04 | 3.1 | 0.7 |
| 10 | 7/1.35 | 4.1 | 0.7 |
| 16 | 7/1.70 | 5.1 | 0.7 |
| 25 | 7/2.14 | 6.4 | 0.9 |
| 35 | 19/1.53 | 7.7 | 0.9 |
| 50 | 19/1.78 | 8.9 | 1.0 |
| 70 | 19/2.14 | 10.7 | 1.1 |
| 95 | 19/2.52 | 12.6 | 1.1 |
| 120 | 37/2.03 | 14.2 | 1.2 |
| 150 | 37/2.25 | 15.8 | 1.4 |
| 185 | 37/2.52 | 17.6 | 1.6 |
| 240 | 61/2.25 | 20.3 | 1.7 |
| 300 | 61/2.52 | 22.7 | 1.8 |
| 400 | 61/2.85 | 25.7 | 2.0 |
| 500 | 61/3.20 | 28.8 | 2.2 |
| 630 | 127/2.52 | 32.8 | 2.4 |
| 800 | 127/2.85 | 37.1 | 2.6 |
| 1000 | 127/3.20 | 41.6 | 2.8 |
| Two-core | |||
| 1.5 | 7/0.53 | 1.6 | 0.7 |
| 2.5 | 7/0.67 | 2.0 | 0.7 |
| 4 | 7/0.85 | 2.6 | 0.7 |
| 6 | 7/1.04 | 3.1 | 0.7 |
| 10 | 7/1.35 | 4.1 | 0.7 |
| 16 | 7/1.70 | 5.1 | 0.7 |
| 25 | 7/2.14 | 6.4 | 0.9 |
| 35 | 19/1.53 | 7.7 | 0.9 |
| 50 | 19/1.78 | 8.9 | 1.0 |
| 70 | 19/2.14 | 10.7 | 1.1 |
| 95 | 19/2.52 | 12.6 | 1.1 |
| Three-core | |||
| 1.5 | 710.53 | 1.6 | 0.7 |
| 2.5 | 710.67 | 2.0 | 0.7 |
| 4 | 7/0.85 | 2.6 | 0.7 |
| 6 | 7/1.04 | 3.1 | 0.7 |
| 10 | 7/1.35 | 4.1 | 0.7 |
| 16 | 7/1.70 | 5.1 | 0.7 |
| 25 | 7/2.14 | 6.2 | 0.9 |
| 35 | 19/1.53 | 7.3 | 0.9 |
| 50 | 19/1.78 | 8.5 | 1.0 |
| 70 | 19/2.14 | 10.1 | 1.1 |
| 95 | 19/2.52 | 11.8 | 1.1 |
| 120 | 37/2.03 | 13.0 | 1.2 |
| 150 | 3712.25 | 14.4 | 1.4 |
| 185 | 37/2.52 | 16.2 | .6 |
| 240 | 61/2.25 | 18.8 | 1.7 |
| 300 | 61/2.52 | 21.3 | 1.8 |
| 400 | 61/2.85 | 24.3 | 2.0 |
| Four-core | |||
| 1.5 | 7/0.53 | 1.6 | 0.7 |
| 2.5 | 7/0.67 | 2.0 | 0.7 |
| 4 | 7/0.85 | 2.6 | 0.7 |
| 6 | 7/1.04 | 3.1 | 0.7 |
| 10 | 7/1.35 | 4.1 | 0.7 |
| 16 | 7/1.70 | 5.1 | 0.7 |
| 25 | 7/2.14 | 6.2 | 0.9 |
| 35 | 19/1.53 | 7.3 | 0.9 |
| 50 | 19/1.78 | 8.5 | 1.0 |
| 70 | 19/2.14 | 10.1 | 1.1 |
| 95 | 19/2.52 | 11.8 | 1.1 |
| 120 | 37/2.03 | 13.0 | 1.2 |
| 150 | 37/2.25 | 14.4 | 1.4 |
| 185 | 37/2.52 | 16.2 | .6 |
| 240 | 61/2.25 | 18.8 | 1.7 |
| 300 | 61/2.52 | 21.3 | 1.8 |
| 400 | 61/2.85 | 24.3 | 2.0 |
| Five-core | |||
| 1.5 | 7/0.53 | 1.6 | 0.7 |
| 2.5 | 710.67 | 2.0 | 0.7 |
| 4 | 7/0.85 | 2.6 | 0.7 |
| 6 | 7/1.04 | 3.1 | 0.7 |
| 10 | 7/1.35 | 4.1 | 0.7 |
| 16 | 7/1.70 | 5.1 | 0.7 |
| 25 | 7/2.14 | 6.2 | 0.9 |
| 35 | 19/1.53 | 7.3 | 0.9 |
| 50 | 19/1.78 | 8.5 | 1.0 |
| 70 | 19/2.14 | 10.0 | 1.1 |
| 95 | 19/2.52 | 11.8 | 1.1 |
| 120 | 37/2.03 | 13.0 | 1.2 |
| 150 | 37/2.25 | 14.4 | 1.4 |
| 185( | 37/2.52 | 16.2 | 1.6 |
| *For two and more core cables, the conductor is circular compact stranded when the conductor area is ≥25mm². *The information in this datasheet is for reference only and is subject to change without notice or liability. |
|||